Description / Applications
The Beckett GeniSys
TM
Advanced Burner Control is a
120 Vac primary safety control for residential and light
commercial oil burners used in boiler, furnace, and
water heater applications having ring rates less than
20 GPH. The GeniSys is used with a suitable cad cell
ame sensor to control the oil burner motor, igniter,
and optional solenoid valve. It has 24 Vac thermostat
terminals (if applicable) compatible with both mechanical
and many power stealing thermostats. It can also provide
interrupted or intermittent duty ignition.
PARTS & ACCESSORIES
GeniSys
120V
Model 7505
Advanced Burner Control
Seitenansicht 0
1 2 3 4 5 6 ... 11 12

Inhaltsverzeichnis

Seite 1 - Model 7505

Description / ApplicationsThe Beckett GeniSysTM Advanced Burner Control is a 120 Vac primary safety control for residential and light commercial oil b

Seite 2 - Features

10If the burner is in the below state:Pushing the reset button will:Button Click(press < 1 second)Button Hold(press > 1 second)Button Hold (pres

Seite 3

11120v GeniSys Control Installation and Operation Manualautomatically return to standby mode. If prime is not established during the four minute pump

Seite 4 - Installation/Operation/

Form No. 61649 R14, Printed in USA 10/10CORPORATIONUSA: P.O. Box 1289 ● Elyria, OH 44036Canada: R.W. Beckett Canada, Ltd. ● Unit #3, 430 Laird Road

Seite 5 - Mounting:

2Table 1 - Models and Cross Reference GuideBeckett GeniSysControl Part No.LockoutTimeValve-ondelay time2Motor-offdelay time2Replaces Honeywell:Replace

Seite 6 - Typical Boiler Wiring:

3120v GeniSys Control Installation and Operation ManualOptional Snap-on Display Module: For programming and diagnosticsOptional Snap-on Alarm Module:

Seite 7 - Typical Furnace Wiring:

4Electrical RatingsInputs:Voltage: 120 Vac nominal (102 to 132 Vac)Current: 100 mA nominal (150 mA max at 132 Vac)Frequency: 60 HzOutputs:Motor: 120 V

Seite 8 - Startup / Checkout

5120v GeniSys Control Installation and Operation ManualThe control can malfunction if it gets wet, leading to accumulation of oil or explosive oil vap

Seite 9 - Sequence of Operation

6Figure 3 – 7505A (for replacement of R7184A)Interrupted ignition, no valve-on or motor-off delay►Figure 4 – 7505B (for replacement of R7184B)Interrup

Seite 10 - Priming the Pump

7120v GeniSys Control Installation and Operation ManualTypical Furnace Wiring:Figure 6 – 7505A (for replacement of R8184G)Intermittent ignition, no va

Seite 11 - Maintenance

8Startup / CheckoutIf the burner or control fails any of the following tests, recheck control wiring. If the burner or control still fails any tests,

Seite 12 - Limited Warranty Information

9120v GeniSys Control Installation and Operation Manual21356847StandbyMotor-off delayValve-on delayTrial forignitionIgnition carryoverRunLockoutRecycl