RWB 664850 Page 3 Printed in U.S.A.
If after the re-rate factor is used the required firing rate input exceeds the Adjusted
Maximum Firing Rate for the burner model being applied, a burner model with a higher
Adjusted Maximum Firing Rate will be required.
For this example
: If an appliance operating at 7000 ft. elevation requires a firing rate
input of 2.75 gph, an SF or CF375 burner may be required instead of an AFG burner.
EXAMPLE 2
R
E-RATING OF THE MAXIMUM FIRING RATE FOR FIXED-TYPE BURNER HEAD @ 7000 FT.
Burner
Model
Head
Maximum Firing
Rate of Head
X
Elevation Re-rate
Factor @ 7000 ft.
=
Adjusted Maximum
Firing Rate of Head
AFG F3 1.25 gph X 87.1% = 1.09 gph
AFG F6 1.65 gph X 87.1% = 1.44 gph
AFG F12 2.00 gph X 87.1% = 1.74 gph
AFG F22 2.50 gph X 87.1% = 2.18 gph
AFG F31 3.00 gph X 87.1% = 2.61 gph
AFG L1 1.10 gph X 87.1% = 0.96 gph
T
O PROVIDE ADEQUATE OXYGEN IN THE COMBUSTION AIR TO MAINTAIN THE FIRING RATE FOR THE
HEATING LOAD
:
If after the re-rate factor is used the required firing rate input exceeds the Adjusted
Maximum Firing Rate for the burner head being applied, a burner head with a higher
Adjusted Maximum Firing rate may be required.
For this example
: If an AFG burner operating at 7000 ft. elevation requires a firing rate
input of 1.15 gph, an F6 head may be required instead of an F3 head.
EXAMPLE 3
R
E-RATING OF THE MAX. FIRING RATE FOR ADJUSTABLE-TYPE BURNER HEAD SETTING @ 7000 FT.
Burner
Model
Head
Head
Setting
Max. Firing Rate
at Head Setting
X
Elevation Re-rate
Factor
=
Adjusted Max. Firing
Rate at Head Setting
AFG V1 1 1.50 gph X 87.1% = 1.31 gph
AFG V1 2 1.75 gph X 87.1% = 1.52 gph
AFG V1 3 2.25 gph X 87.1% = 1.96 gph
AFG V1 4 2.50 gph X 87.1% = 2.18 gph
AFG V1 5 2.75 gph X 87.1% = 2.40 gph
T
O PROVIDE ADEQUATE OXYGEN IN THE COMBUSTION AIR TO MAINTAIN THE FIRING RATE FOR THE
HEATING LOAD
: