RWB 664850 Page 4 Printed in U.S.A.
• If after the re-rate factor is used the required firing rate input exceeds the Adjusted
Maximum Firing Rate for the head setting, a head setting for a higher Adjusted
Maximum Firing rate may be required.
For this example
: If an AFG burner using a V1 head operating at 7000 ft. elevation
requires a firing rate input of 1.40 gph, a change of head setting from 1 to 2 may be
required.
EXAMPLE 4
R
E-RATING OF THE MAX. FIRING RATE FOR ADJUSTABLE-TYPE BURNER HEAD SETTING @ 7000 FT.
Burner
Model
Head
Head
Setting
Max. Firing Rate
at Head Setting
X
Elevation Re-rate
Factor
=
Adjusted Max. Firing
Rate at Head Setting
CF375 SL1 0 1.65 gph X 87.1% = 1.44 gph
CF375 SL1 1 1.75 gph X 87.1% = 1.52 gph
CF375 SL1 3 2.00 gph X 87.1% = 1.74 gph
CF375 SL1 4 2.50 gph X 87.1% = 2.18 gph
CF375 SL1 5 3.00 gph X 87.1% = 2.61 gph
CF375 SL1 6 3.75 gph X 87.1% = 3.27 gph
Note: The above settings are approximate, and can vary depending on actual job conditions
and overfire pressure.
T
O PROVIDE ADEQUATE OXYGEN IN THE COMBUSTION AIR TO MAINTAIN THE FIRING RATE FOR THE
HEATING LOAD
:
• If after the re-rate factor is used the required firing rate input exceeds the Adjusted
Maximum Firing Rate for the head setting, a head setting for a higher Adjusted
Maximum Firing rate may be required.
For this example
: If a CF375 burner using an SL1 head operating at 7000 ft. elevation
requires a firing rate input of 2.25 gph, a change of head setting from 4 to 5 may be
required.
Remember--it is important to maintain the BTU input as required by the installation and
specified by the furnace or boiler manufacturer. If you need further assistance, please contact
Beckett Technical Service at 1-800-645-2876 or e-mail our Technical Service Department at